7.10 Rake (screen) control
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
133
7.10.2
Setting common parameters
Prerequisite:
Substitute the details of your application in place of the sample values provided. If you are
bench testing the unit, set your test values to be the same as the sample values.
Parameter
Index
Mode/Value
Description
(Page 163)
Global
(Page 163)
Operation=Differential
(Page 165)
Global
Material=Liquid
(Page 174)
1 & 2
(Page 174)
Max. Process Speed=Medium
(Page 164)
1 & 2
XPS-10 (single-point pre-
set)
Transducer=XPS-10
(Page 162)
Global
1
Units=Meters
(Page 170)
1
1.8
Empty=1.8 m
2
2.2
Empty=2.2 m
(Page 169)
1
1.4
Span=1.4 m
2
1.4
Span=1.4 m
3
1.4
Max Differential=1.4 m
7.10.3
Set Relay 1 (Operate Rake)
Parameter
Index
Mode/value
Description
(Page 194)
1
Difference or average
Starts the rake when the
difference between the two
levels rises above 0.4 m and
stops the rake when the
difference falls below 0.1 m.
(Page 195)
1
Fixed Duty Assist
(Page 197)
1
0.4
(Page 197)
1
0.1