Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
71
Dimension L
Length of the cylindrical section of a horizontal parabolic end vessel.
Dimension L as used in Vessel shape (2.7.2.) (Page 186).
Index
Level
Values
Range: 0.0 ... 99.00 m or equivalent, depending on Units (2.1.1.) (Page 162).
Preset: 0.000
Enter: Tank length (excluding both end sections) if Vessel Shape (2.7.2.) (Page 186) =
Parabolic Ends.
Maximum volume
The maximum volume of the vessel.
Enter the vessel volume corresponding to Span (2.2.2.) (Page 169). For example, if your
maximum vessel volume is 8000 L, enter a value of 8000.
For readings in volumetric units (rather than percent), enter the equivalent vessel volume for
Span (2.2.2.) (Page 169).
Index
Level
Values
Range: 0.000 ... 99999
Preset: 100.0
Any volume units can be chosen because volume is calculated from empty to maximum
span, and is scaled according to the Vessel shape (2.7.2.) (Page 186) value.
Note
Ensure the selected units allow LCD volume display.
Example:
•
If max. volume = 3650 m
3
, enter 3650
•
If max. volume = 267500 gallons, enter 267.5 (thousands of gallons)
Summary of Contents for HydroRanger 200 HMI
Page 2: ......
Page 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Page 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Page 362: ......
Page 403: ......