Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
69
Units
Sensor measurement units
Options
*M (meters)
CM (centimeters)
MM (millimeters)
FT (feet)
IN (inches)
Note
For the purpose of this example, all values are assumed to be in meters.
Empty
Sets the distance from the face of the transducer to the process empty point
Index
Level
Values
Range: 0.000 ... 99.000 m
Preset: 5.000 m
Span
Sets the range to be measured
Index
Level
Options
Range: 0.000 ... 99.000 m [or equivalent, depending on Units (2.1.1.) (Page 162)
]
Preset: based on Empty (2.2.4.) (Page 170)