Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
173
8.6.3.2
Fill rate/minute (2.3.2.)
Adjusts the device’s response to increases in the actual material level [or advance to a
higher Material Level (2.4.5.) (Page 178)].
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0.000 ... 99.00 m [or equivalent, depending on Units (2.1.1.) (Page 162)]
Preset: 20% of Span (2.2.2.)
Altered by
Response Rate (2.3.4.) (Page 174)
Related
•
Units (2.1.1.) (Page 162)
•
Span (2.2.2.) (Page 169)
•
Material level (2.4.5.) (Page 178)
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(2.1.1.) (Page 162) per minute, is automatically altered when Response Rate (2.3.4.)
(Page 174) is altered.
Response rate (2.3.4.) value
Meters/minute
1
0.1
2
1
3
10
8.6.3.3
Empty rate/minute (2.3.3.)
Adjusts the device’s response to decreases in the actual material level [or advance to a
lower Material Level (2.4.5.) (Page 178)].
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0.000 ... 99.00 m [or equivalent, depending on Units (2.1.1.) (Page 162)]
Altered by
Response Rate (2.3.4.) (Page 174)
Related
•
Units (2.1.1.) (Page 162)
•
Span (2.2.2.) (Page 169)
•
Material level (2.4.5.) (Page 178)
Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units
(2.1.1.) (Page 162) per minute, is automatically altered when Response Rate (2.3.4.)
(Page 174) is altered.
Response rate (2.3.4.) value
Meters/minute
1
0.1
2
1
3
10