Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
251
8.6.14.4
Running totalizers low (2.14.3.)
Shows and/or alters the four least significant digits of the totalizer value.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0 ... 9999
Related
•
Running totalizers high (2.14.2.) (Page 250)
•
Totalizer decimal position (2.14.4.) (Page 251)
•
Totalizer multiplier (2.14.5.) (Page 252)
8.6.14.5
Totalizer decimal position (2.14.4.)
Sets the maximum number of decimal places to be displayed.
Index
Single-point model
Dual-point model
Global
Transducer
Options
No digits
1 digit
*2 digits
3 digits
Related
•
Running totalizers high (2.14.2.) (Page 250)
•
Running totalizers low (2.14.3.) (Page 251)
Note
Set the decimal position during initial commissioning of the device. If the position is changed
later, the totalizer data in Running Totalizer High (2.14.2.) (Page 250) and Running Totalizer
Low (2.14.3.) (Page 251) will be incorrect and must be reset according to the new decimal
value.
In RUN mode, the number of decimal places displayed is not automatically adjusted. When
the LCD Total value is so large as to exceed display capabilities, the total rolls over to 0 and
continues incrementing.