HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
351
Updating software
D
Please contact your Siemens representative to obtain the software update for the device. A
complete list of representatives is available here: www.siemens.com/processinstrumentation
www.siemens.com/processinstrumentation
), and choose Service on the right side.
Note
1. All parameter values will be lost during software update. Record your current parameters
manually or using SIMATIC PDM before updating.
2. Disable all pumps and alarms before updating software, as relays can change state during
the procedure, causing pumps to turn ON or OFF.
To install the software, please complete the following:
1.
Connect your PC or laptop to the device's RJ-11 RS-232 port.
2.
Run the .exe Downloader program in the software. Use this to make the RS-232 settings
match your device. Please note that the software default settings will already match the
default settings of the unit. Changes are only necessary if the RS-232 settings in the unit
have been changed.
3.
Complete the Downloader program steps.
4.
Verify that Downloader confirms a successful upgrade before exiting.
5.
Complete a master reset [Master Reset (3.2.3.) (Page 254)] after a successful upgrade
before re-entering parameters.