Diagnosing and troubleshooting
10.2 General fault codes
HydroRanger 200 HMI
282
Operating Instructions, 06/2018, A5E36281317-AC
10.2
General fault codes
Note
If two faults are present at the same time, the device status indicator and text for the fault
with the higher priority will display.
HMI icon
Priority
Fault #
Fault text
Cause
1
14
Trans. 1 Loss of Echo
Point 1 fail-safe.
2
15
Trans. 2 Loss of Echo
Point 2 fail-safe.
3
1
TS-3 short (TB:28/29)
TS-3 terminals shorted.
4
2
Trans. 1 open (TB:1/2)
Transducer 1 open.
5
3
Trans. 2 open (TB:3/4)
Transducer 2 open.
6
4
Trans. 1 short (TB:1/2)
Transducer 1 short.
7
5
Trans. 2 short (TB:3/4)
Transducer 2 short.
8
6
Trans. 1 short (TB:1/2)
Transducer 1 short.
9
7
Trans. 2 short (TB:3/4)
Transducer 2 short.
10
8
Trans. 1 error (TB:1/2)
Transducer 1 specified incorrectly,
connections reversed, faulty inter-
nal temp sensor.
11
9
Trans. 2 error (TB:3/4)
Transducer 2 specified incorrectly,
connections reversed, faulty inter-
nal temp sensor.
12
10
Point 1 Temp. open
Temp sensor assigned to Point 1
open.
13
11
Point 2 Temp. open
Temp sensor assigned to Point 2
open.
14
12
Point 1 Temp. Error
Temp sensor assigned to Point 1
reversed, shorted cable, temp
sensor failed.
15
13
Point 2 Temp. Error
Temp sensor assigned to Point 2
reversed, shorted cable, temp
sensor failed.