Operating
7.9 Pump control
HydroRanger 200 HMI
130
Operating Instructions, 06/2018, A5E36281317-AC
7.9.4.8
Grouping pumps
You can group pumps and use the same pumping algorithm separately on each group. If you
specify different pumping algorithms, then you do not need to use this parameter because
the pumps are already grouped by algorithm.
Group pumps only when four pumps are using the same algorithm, and you want to split
them into two groups.
Example:
Pumps 1 and 2 will operate as a group, and Pumps 3 and 4 will operate as another group.
Parameter
Index
Mode
Description
(Page 201)
1
Groups Pumps 1 and 2
(Page 201)
2
(Page 201)
3
Groups Pumps 3 and 4
(Page 201)
4
7.9.4.9
Setting a flush valve
A flush valve stirs up the sediment at the bottom of the well during pumping, so that it doesn’t
accumulate. These parameters will control any relays set with Relay Function (2.8.1.4.)
(Page 195) = Flush Valve. Most sets of parameters will work with only one or two changes;
however, for these parameters to work, all of them must be set to a value.
Example:
The flush valve connects to Relay 4 and the watched pump is on Relay 1.
Parameter
Index
Value
Description
(Page 216)
-
4
Flush valve is connected to Relay 4
(Page 216)
Global
1
Watch Relay 1 to count pump cycles
(Page 217)
Global
3
Open the flush valve for 3 cycles
(Page 217)
Global
10
Use the flush value every 10 cycles
(Page 217)
Global
120
Open the flush valve for 120 seconds