Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
63
Operation
Sets the type of measurement (and the corresponding mA output) required for the
application.
Mode
Description
Reference point
Out of Service
Level Point is not activated
Not applicable
Level
Height of material
Empty (2.2.4.) (Page 170)
Space
Distance to material surface
Span (2.2.2) (Page 169)
Distance
Sensor reference point
①
Distance
④
Span (2.2.2.) (Page 169)
②
Space
⑤
Empty (2.2.4.) (Page 170)
③
Sensor reference point
⑥
Level
Temperature source
Selects the source of the temperature reading used to adjust the speed of sound.
Index
Transducer
Options
*AUTO
Fixed Temperature
Transducer
External TS-3
Average of Sensors
For more information, see Temperature source (2.11.1.4.) (Page 219).
Fixed Temperature
Sets the temperature of the source when there is no temperature-sensing device connected.
This parameter only displays if Fixed Temperature is selected for Temperature Source.
Value
Range: -100.0 ... +150.0 °C
Default: +20.0 °C