Operating
7.3 Relays
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
103
Screen
Note
Before activating this preset, Sensor Mode (2.1.3.) (Page 163) must be set to Dual-Point
Difference, and Span (2.2.2.) (Page 169) for Level 3 must be set.
Differential control of a screen or rake:
Parameter
Relay #
1
2
3
4
5
6
(2.8.1.2.) (Page 194)
Difference or
average
Transducer
1
Transducer
2
Difference
or average
OFF OFF
(2.8.1.4.) (Page 195)
Fixed Duty Assist Level (H)
Level (L)
Level (H)
--
--
(Page 197)
80%
90%
10%
90%
--
--
(2.8.1.6.) (Page 197)
20%
85%
15%
10%
--
--
Alarms
General alarms at four setpoints:
Parameter
Relay #
1
2
3
4
5
6
(2.8.1.4.) (Page 195)
Level (H)
Level (L)
Level (HH)
Level (LL) OFF
OFF
(2.8.1.5.) (Page 197)
80%
20%
90%
10%
--
--
(2.8.1.6.) (Page 197)
75%
25%
85%
15%
--
--