Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
82
Operating Instructions, 06/2018, A5E36281317-AC
Configure another measurement point
Gives option to configure more measurement points or end the wizard.
Note
This is available on the dual-point model only.
Options
Yes
Returns to the Measurement Point menu
No
Completes the Quick Start Volume configuration
End of QS Volume Wizard
Note
For Quick Start to be successful, all changes must be applied.
Options
BACK, CANCEL, FINISH
Display returns to Quick Start (1.1.) menu when Quick Start is successfully com-
pleted or cancelled. If CANCEL is selected, no changes are written to the device.
To transfer Quick Start values to the device and return to PROGRAM menu, press DOWN
arrow (Finish). Then press LEFT arrow three times to return to Measurement mode.
Note
It is strongly recommended that an Auto Zero Head be performed after completion of the
wizard to ensure best accuracy. For more information see Auto Zero Head (2.13.3.)
(Page 240).