Operating
7.9 Pump control
HydroRanger 200 HMI
122
Operating Instructions, 06/2018, A5E36281317-AC
Set the Relay ON Setpoints
Parameter
Index
Value
Description
(Page 197)
1
0.4 m
Sets the three setpoints for the
pump relays. The setpoints
remain attached to the pump
relays.
(Page 197)
2
0.3 m
(Page 197)
3
0.2 m
Set the Relay OFF Setpoints
Parameter
Index
Value
Description
(Page 197)
1
1.3 m
Sets the three setpoints for the
pump relays.
(Page 197)
2
1.3 m
(Page 197)
3
1.3 m
7.9.3.3
Set relays to Fixed Duty Backup
Parameter
Index
Mode
Description
(Page 195)
1
Fixed Duty Backup
Sets the pump relays (Relays 1,
2, and 3) to Fixed Duty Backup.
Only one pump will ever run at
one time.
(Page 195)
2
Fixed Duty Backup
(Page 195)
3
Fixed Duty Backup
Set the Relay ON Setpoints
Parameter
Index
Value
Description
(Page 197)
1
0.4 m
Sets the three setpoints for the
pump relays. The setpoints
remain attached to the pump
relays.
(Page 197)
2
0.3 m
(Page 197)
3
0.2 m