Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
179
8.6.4.6
Fail-safe advance (2.4.6.)
Sets the speed the device advances to, and returns from, the Fail-safe Material Level.
Index
Level
Options
*Restricted
Advances to/from Fail-safe Material Level as set by
•
Response Rate (2.3.4.) (Page 174)
•
Fill rate/minute (2.3.2.) (Page 173)
•
Empty rate/minute (2.3.3.) (Page 173)
Immediate
Fail-safe Material Level assumed right away.
Fast back
Fail-safe Level Advance is restricted, return is immedi-
ate.
Related
•
Response rate (2.3.4.) (Page 174)
•
LOE timer (2.4.2.) (Page 177)
•
Material level (2.4.5.) (Page 178)
•
Fill rate/minute (2.3.2.) (Page 173)
•
Empty rate/minute (2.3.3.) (Page 173)
8.6.4.7
mA Output selector (2.4.7.)
Sets the mA Output index for all applicable parameters in this sub-menu
.
Options
*mA Output 1
mA Output 2
8.6.4.8
mA Fail-safe mode (2.4.8.)
Use for fail-safe operation, independent of the Material Level (2.4.5.) (Page 178).
Index
mA Output
Options
*OFF
mA output responds to Material level (2.4.5.) (Page 178).
HI
Produce the Span mA output immediately.
LO
Produce the Empty mA output immediately.
Hold
Last known value is held until normal operation resumes.
Value
mA output goes to user-selected value defined in mA Fail-safe
Value (2.4.9.) (Page 180)
Related