Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
76
Operating Instructions, 06/2018, A5E36281317-AC
Span
Sets the range to be measured
Index
Level
Options
Range: 0.000 ... 99.000 m [or equivalent, depending on Units (2.1.1.) (Page 162)
]
Preset: based on Empty (2.2.4.) (Page 170)
Response rate
Sets the reaction speed of the device to measurement changes in the target range.
Note
•
Any changes made to Fill rate/minute (2.3.2.) (Page 173), Empty rate/minute (2.3.3.)
(Page 173), or Response rate (2.3.4.) (Page 174) parameters following the completion of
the wizard will supersede the Response Rate setting.
•
Response Rate always displays in meters per minute (m/min).
Index
Transducer
Options
Slow (0.1 m/min)
*Medium (1.0 m/min)
Fast (10.0 m/min)
Factory setting
Medium (1.0 m/min)
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy, faster settings allow for more rapid level
fluctuations.
Primary measuring device
The type of primary measuring device (PMD) used.
Index
Single-point model
Dual-point model
Global
Transducer
Options
1)
OFF
Exponential devices
see Flow exponent (2.13.4.1) (Page 241)
Palmer-Bowlus Flume
see PMD dimensions (2.13.5.) (Page 246)
H-Flume
Rectangular Flume BS- 3680
Thin Plate V-Notch Weir BS-3680
1)
Option will be set to Other if the wizard was run previously and the device was set to OFF
or Universal Head vs. Flow. If this is the initial configuration, the PMD can only be set for no
calculation (OFF), or for linearization (Universal Head vs. Flow).