Operating
7.9 Pump control
HydroRanger 200 HMI
118
Operating Instructions, 06/2018, A5E36281317-AC
7.9.1.1
Set relays to Alternate Duty Assist
Parameter
Index
Mode
Description
(Page 195)
1
Alternate Duty Assist Sets the pump relays (Re-
lays 1, 2, and 3) to Alternate
Duty Assist.
(Page 195)
2
Alternate Duty Assist
(Page 195)
3
Alternate Duty Assist
7.9.1.2
Set the ON setpoints
Parameter
Index
Value
Description
(Page 197)
1
1.0 m
Sets the three setpoints for the pump
relays. The first cycle will use these
setpoints. Subsequent cycles rotate
the setpoints among the pumps.
(Page 197)
2
1.1 m
(Page 197)
3
1.2 m
7.9.1.3
Set the OFF setpoints
Parameter
Index
Value
Description
(Page 197)
1
0.5 m
Sets the three setpoints for the pump
relays. The first cycle will use these
setpoints. Subsequent cycles rotate
the setpoints among the pumps.
(Page 197)
2
0.5 m
(Page 197)
3
0.5 m