Operating
7.9 Pump control
HydroRanger 200 HMI
124
Operating Instructions, 06/2018, A5E36281317-AC
7.9.3.5
Set relays to First in First Out
Parameter
Index
Mode
Description
(Page 195)
1
FIFO
Sets the pump relays (Relays 1,
2, and 3) to First In First Out.
(Page 195)
2
FIFO
(Page 195)
3
FIFO
Set the Relay ON Setpoints
Parameter
Index
Value
Description
(Page 197)
1
0.4 m
Sets the three setpoints for the
pump relays. The first cycle will
use these setpoints. Subse-
quent cycles rotate the set-
points among the pumps.
(Page 197)
2
0.3 m
(Page 197)
3
0.2 m
Set the Relay OFF Setpoints
Parameter
Index
Value
Description
(Page 197)
1
1.3 m
Sets the three setpoints for the
pump relays.
(Page 197)
2
1.3 m
(Page 197)
3
1.3 m