Operating
7.3 Relays
HydroRanger 200 HMI
100
Operating Instructions, 06/2018, A5E36281317-AC
7.3.9
Preset applications
Preset applications set up the relay parameters to predetermined values shown below:
OFF: all relays set to OFF
Wet Well 1
Pump down with the following settings:
Parameter
Relay #
1
2
3
4
5
6
(Page 195)
Alternate Duty
Assist
Alternate Duty
Assist
Level (H)
Level (L)
OFF
OFF
(Page 197)
70%
80%
90%
10%
--
--
(Page 197)
20%
20%
85%
15%
--
--