Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
182
Operating Instructions, 06/2018, A5E36281317-AC
8.6.5.5
4 mA setpoint (2.5.5.)
Sets the process level corresponding to the 0 or 4 mA value.
Index
mA Output
Values
Range: -999 ... 9999
Related
20 mA setpoint (2.5.6.) (Page 182)
Enter the value [in applicable Units (2.1.1.) (Page 162)] to correspond to 0 or 4 mA.
8.6.5.6
20 mA setpoint (2.5.6.)
Sets the process level that corresponds to the 20 mA value.
Index
mA Output
Values
Range: -999 ... 9999
Related
4 mA setpoint (2.5.5.) (Page 182)
Enter the value [in applicable Units (2.1.1.) (Page 162)] to correspond to 20 mA.
8.6.5.7
Minimum mA limit (2.5.7.)
Sets the minimum mA output value to be produced.
Index
mA Output
Values
Range: 0.000 .. 22.000 mA
Preset: 3.800 mA
Related
•
mA output range (2.5.2.) (Page 180)
•
Maximum mA limit (2.5.8.) (Page 182)
8.6.5.8
Maximum mA limit (2.5.8.)
Sets the maximum mA output value to be produced.
Index
mA Output
Values
Range: 0.000 ... 22.000 mA
Preset: 20.200 mA
Related
•
mA output range (2.5.2.) (Page 180)
•
Minimum mA limit (2.5.7.) (Page 182)
8.6.5.9
Milliamp output (2.5.9.)
Displays the current mA output value.
Range: 3.500 ... 22.2 mA