Operating
7.9 Pump control
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
127
7.9.4.3
Totalizing pumped volume
Prerequisite: The volume of the vessel must be known.
Parameter
Index
Mode/Value
Description
(Page 163)
Global
Pump Totalizer
Operation = Pumped volume
Material (2.1.6.) (Page 165) Global
*Liquid
These parameters are as
shown above.
(Page 174)
Global
*Medium (1.0 m/ min)
(Page 164)
Global
XPS-10 (singlepoint
preset)
Units (2.1.1.) (Page 162)
Global
Meters
Empty (2.2.4.) (Page 170) Global
1.8
Span (2.2.2.) (Page 169)
Global
1.4
(Page 186)
Global
Flat Level Bottom
Tank shape is Flat Level Bot-
tom.
(Page 188)
Global
17.6
Max volume is 17.6 m
3
or
17,600 liters.
(Page 195)
1
Alternate Duty Assist
Sets Relays 1, 2, and 3 as a
pump group using Alternate
Duty Assist.
(Page 195)
2
Alternate Duty Assist
(Page 195)
3
Alternate Duty Assist
(Page 197)
1
1.0
Sets the ON setpoints for the
pump group.
(Page 197)
2
1.2
(Page 197)
3
1.4
(Page 197)
1
0.2
Sets the OFF setpoints for the
pump group.
(Page 197)
2
0.2
(Page 197)
3
0.2
Set in RUN Mode
1.
Press the LEFT arrow to go to Measurement View mode.
2.
Once there, press the DOWN arrow to show Measurement View 2.
3.
Press the LEFT arrow until Totalizer is shown.