Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
184
Operating Instructions, 06/2018, A5E36281317-AC
8.6.6
Current Input (2.6.)
8.6.6.1
mA input range (2.6.1.)
Shows the mA input range of the connected mA device.
Index
Global
Options
0 ... 20 mA
*4 ... 20 mA
Ensure this range corresponds to the output range of the external device. All level
measurements will equate % of Span with the % of the mA range.
8.6.6.2
0/4 mA level value (2.6.2.)
Shows the process level corresponding to the 0 or 4 mA value.
Index
Global
Values
Range: -999 ... 9999%
Preset: 0%
Related
•
Empty (2.2.4.) (Page 170)
•
Span (2.2.2.) (Page 169)
When using an external mA signal to determine level, the input range must be scaled to give
accurate results.
8.6.6.3
20 mA level value (2.6.3.)
Shows the process level corresponding to the 20 mA value.
Index
Global
Values
Range: -999 ... 9999%
Preset: 100%
Related
•
Empty (2.2.4.) (Page 170)
•
Span (2.2.2.) (Page 169)
Input range is scaled for accuracy if an external mA signal calculates level.