Parameter reference
8.6 Setup (2.)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
175
8.6.3.5
Rate filter (2.3.5.)
Damps the Flow Maximum (3.2.8.15.) (Page 259) fluctuations
Index
Single-point model
Dual-point model
Global
Transducer
Options
Rate display not required
Filtered Output: Continuous filtering and update
Interval Output:
*1 min or 50 mm (2 in)
5 min or 100 mm (3.9 in)
10 min or 300 mm (11.8 in)
10 min or 1000 mm (39.4 in)
Alters
Flow Maximum (3.2.8.15.) (Page 259)
Altered by
Response Rate (2.3.4.) (Page 174)
Related
Rate Filter Time (2.3.6.) (Page 175)
Rate Filter Distance (2.3.7.) (Page 175)
Enter the time or distance interval over which the Flow Maximum (3.2.8.15.) (Page 259) is to
be calculated before the display updates.
This is automatically altered along with Response Rate (2.3.4.) (Page 174).
This value automatically alters the Rate Filter Time (2.3.6.) (Page 175) and/or Rate Filter
Distance (2.3.7.) (Page 175). Alternatively, these parameter values may be altered
independently.
8.6.3.6
Rate filter time (2.3.6.)
The time period, in seconds, over which the material level rate of change is averaged before
Flow Maximum (3.2.8.15.) (Page 259) updates.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0.000 ... 9999 seconds
Related
Flow Maximum (3.2.8.15.) (Page 259)
8.6.3.7
Rate filter distance (2.3.7.)
The material level change, in meters, to initiate a Flow Maximum (3.2.8.15.) (Page 259)
update.
Index
Single-point model
Dual-point model
Global
Transducer
Values
Range: 0.000 ... 9999 meters
Related
Flow Maximum (3.2.8.15.) (Page 259)