Commissioning
6.5 Quick Start Wizards
HydroRanger 200 HMI
64
Operating Instructions, 06/2018, A5E36281317-AC
Units
Sensor measurement units
Options
*M (meters)
CM (centimeters)
MM (millimeters)
FT (feet)
IN (inches)
Note
For the purpose of this example, all values are assumed to be in meters.
Empty
Sets the distance from the face of the transducer to the process empty point
Index
Level
Values
Range: 0.000 ... 99.000 m
Preset: 5.000 m
Span
Sets the range to be measured
Index
Level
Options
Range: 0.000 ... 99.000 m [or equivalent, depending on Units (2.1.1.) (Page 162)
]
Preset: based on Empty (2.2.4.) (Page 170)
Summary of Contents for HydroRanger 200 HMI
Page 2: ......
Page 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Page 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Page 362: ......
Page 403: ......