Operating
7.9 Pump control
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
123
Set the Relay OFF Setpoint
Parameter
Index
Value
Description
(Page 197)
1
1.3 m
Sets the three setpoints for the
pump relays.
(Page 197)
2
1.3 m
(Page 197)
3
1.3 m
7.9.3.4
Set relays to Service Ratio Duty Assist
Parameter
Index
Mode/Value
Description
(Page 195)
1
Service Ratio Duty Assist
Sets the pump relays (Relays 1,
2, and 3) to Service Ratio Duty
Assist.
(Page 195)
2
Service Ratio Duty Assist
(Page 195)
3
Service Ratio Duty Assist
(Page 200)
1
25
Sets the ratio to:
•
25% – Pump 1
•
50% – Pump 2
•
25% – Pump 3
(Page 200)
2
50
(Page 200)
3
25
Set the Relay ON Setpoints
Parameter
Index
Value
Description
(Page 197)
1
0.4 m
Sets the three setpoints for the
pump relays. The first cycle will
use these setpoints. Subse-
quent cycles rotate the set-
points among the pumps.
(Page 197)
2
0.3 m
(Page 197)
3
0.2 m
Set the Relay OFF Setpoints
Parameter
Index
Value
Description
(Page 197)
1
1.3 m
Sets the three setpoints for the
pump relays.
(Page 197)
2
1.3 m
(Page 197)
3
1.3 m