8. COMMUNICATION DATA LIST
IMR02E20-E1
36
8.2 Communication Data of COM-ML
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX
DEC
1
Instrument number
(COM-ML)
RX CH1
8
RO
M
Serial number (character)
2
Instrument number
(Function module*)
RZ
CH1
CH100
8
RO
M
Serial number (character)
3
Model code
(COM-ML)
ID CH1
32
RO
M
Model code (character)
4
Model code
(Function module*)
IE
CH1
CH100
32
RO
M
Model code (character)
5
ROM version
(COM-ML)
VR CH1
8
RO
M
ROM
version
6
ROM version
(Function module*)
VQ
CH1
CH100
8
RO
M
ROM version
7
Integrated operating
time monitor
(COM-ML)
UT CH1
7
RO
M
0 to 19999 hours
8
Integrated operating
time monitor
(Function module*)
UV
CH1
CH100
7
RO
M
0 to 19999 hours
9
Error code
(COM-ML)
ER CH1 0000
0
7 RO
U
RKC communication
1:
Adjustment data error
1
2:
Data back-up error
4:
A/D conversion error
1
32: Logic output data error
2
64: Stack overflow
3
512: Network module error
3
Modbus
Bit data
Bit 0: Adjustment data error
1
Bit 1: Data back-up error
Bit 2: A/D conversion error
1
Bit 3 and Bit 4: Unused
Bit 5: Logic output data error
2
Bit 6: Stack overflow
3
Bit 7 and Bit 8: Unused
Bit 9: Network module error
3
Bit 10 to Bit 15: Unused
Data
0: OFF
1: ON
[Decimal number: 0 to 615]
The error condition is shown by the
OR
of each module.
When multiple errors occur, the
error No. is the sum value.
1
Only the function module
2
Only the Z-TIO and Z-DIO module
3
Only the COM-ML
10
Error code
(Function module*)
EZ
CH1
CH100
0001
0064
1
100
7 RO
M
11
Backup memory state
monitor
(COM-ML)
EM
CH1 0065 101 1 RO
M 0: The content of the backup
memory does not coincide with
that of the RAM.
1: The content of the backup
memory coincides with that of
the
RAM.
*
Function module: Z-TIO module, Z-DIO module or Z-CT module
Continued on the next page.