8. COMMUNICATION DATA LIST
IMR02E20-E1
58
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
162 Integral time
adjusting factor
[cool-side]
KG CH1
CH64
2C6C
2CAB
11372
11435
7 R/W
C 0.01 to 10.00 times
1.00
163 Derivative time
adjusting factor
[cool-side]
KH CH1
CH64
2CAC
2CEB
11436
11499
7 R/W
C 0.01 to 10.00 times
1.00
164 Proportional band
limiter (high)
[heat-side]
P6 CH1
CH64
2CEC
2D2B
11500
11563
7 R/W
C TC/RTD inputs:
0 (0.0) to Input span
(Unit:
C [
F])
Varies with the setting of the decimal
point
position
selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of input span
0 (0.0): ON/OFF action
(ON/OFF action for both heat and
cool actions in case of a Heat/Cool
PID
control
type.)
TC/RTD:
Input span
V/I: 1000.0
165 Proportional band
limiter (low)
[heat-side]
P7 CH1
CH64
2D2C
2D6B
11564
11627
7 R/W
C
TC/RTD:
0 (0.0)
V/I: 0.0
166 Integral time limiter
(high) [heat-side]
I6 CH1
CH64
2D6C
2DAB
11628
11691
7 R/W
C PID control or Heat/Cool PID
control:
0 to 3600 seconds or 0.0 to
1999.9
seconds
Position proportioning PID control:
1 to 3600 seconds or 0.1 to
1999.9
seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
3600
167 Integral time limiter
(low) [heat-side]
I7 CH1
CH64
2DAC
2DEB
11692
11755
7 R/W
C
PID control,
Heat/Cool PID
control: 0
Position
proportioning
PID control: 1
168 Derivative time
limiter (high)
[heat-side]
D6 CH1
CH64
2DEC
2E2B
11756
11819
7 R/W
C 0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
3600
169 Derivative time
limiter (low)
[heat-side]
D7 CH1
CH64
2E2C
2E6B
11820
11883
7 R/W
C
0
170 Proportional band
limiter (high)
[cool-side]
P8 CH1
CH64
2E6C
2EAB
11884
11947
7 R/W
C TC/RTD inputs:
1(1.0) to Input span
(Unit:
C [
F])
Varies with the setting of the decimal
point
position
selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of input span
TC/RTD:
Input span
V/I: 1000.0
171 Proportional band
limiter (low)
[cool-side]
P9 CH1
CH64
2EAC
2EEB
11948
12011
7 R/W
C
TC/RTD:
1 (0.1)
V/I: 0.1
172 Integral time limiter
(high) [cool-side]
I8 CH1
CH64
2EEC
2F2B
12012
12075
7 R/W
C 0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
3600
173 Integral time limiter
(low) [cool-side]
I9 CH1
CH64
2F2C
2F6B
12076
12139
7 R/W
C
0
174 Derivative time
limiter (high)
[cool-side]
D8 CH1
CH64
2F6C
2FAB
12140
12203
7 R/W
C 0 to 3600 seconds or
0.0 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
3600
175 Derivative time
limiter (low)
[cool-side]
D9 CH1
CH64
2FAC
2FEB
12204
12267
7 R/W
C
0
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Continued on the next page.