8. COMMUNICATION DATA LIST
IMR02E20-E1
57
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
149 Output change rate
limiter (up)
[cool-side]
PX CH1
CH64
292C
296B
10540
10603
7 R/W
C 0.0 to 100.0 % of manipulated
output/seconds
(0.0: OFF)
Becomes invalid when in Position
proportioning PID control.
0.0
150 Output change rate
limiter (down)
[cool-side]
PY CH1
CH64
296C
29AB
10604
10667
7 R/W
C
0.0
151 Output limiter (high)
[cool-side]
OX CH1
CH64
29AC
29EB
10668
10731
7 R/W
C Output limiter low [cool-side] to
105.0 %
105.0
152 Output limiter (low)
[cool-side]
OY CH1
CH64
29EC
2A2B
10732
10795
7 R/W
C
5.0 % to Output limiter high
[cool-side]
5.0
153 AT bias
GB CH1
CH64
2A2C
2A6B
10796
10859
7 R/W
C
Input span to +Input span
Varies with the setting of the decimal
point position.
0 (0.0)
154 AT cycles
G3 CH1
CH64
2A6C
2AAB
10860
10923
1 R/W
C 0: 1.5 cycles
1: 2.0 cycles
2: 2.5 cycles
3: 3.0 cycles
1
155 Output value with
AT turned on
OP CH1
CH64
2AAC
2AEB
10924
10987
7 R/W
C Output value with AT turned off to
105.0 %
Actual output values become those
restricted by the output limiter.
Position proportioning PID control:
Becomes valid only when there is
feedback resistance (FBR) input and it
does not break (high limit of feedback
resistance input at AT).
105.0
156 Output value with
AT turned off
OQ CH1
CH64
2AEC
2B2B
10988
11051
7 R/W
C
105.0 % to Output value with AT
turned on
Actual output values become those
restricted by the output limiter.
Position proportioning PID control:
Becomes valid only when there is
feedback resistance (FBR) input and it
does not break (low limit of feedback
resistance input at AT).
105.0
157 AT differential gap
time
GH CH1
CH64
2B2C
2B6B
11052
11115
7 R/W
C 0.0 to 50.0 seconds
10.0
158 Proportional band
adjusting factor
[heat-side]
KC CH1
CH64
2B6C
2BAB
11116
11179
7 R/W
C 0.01 to 10.00 times
1.00
159 Integral time
adjusting factor
[heat-side]
KD CH1
CH64
2BAC
2BEB
11180
11243
7 R/W
C 0.01 to 10.00 times
1.00
160 Derivative time
adjusting factor
[heat-side]
KE CH1
CH64
2BEC
2C2B
11244
11307
7 R/W
C 0.01 to 10.00 times
1.00
161 Proportional band
adjusting factor
[cool-side]
KF CH1
CH64
2C2C
2C6B
11308
11371
7 R/W
C 0.01 to 10.00 times
1.00
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Continued on the next page.