8. COMMUNICATION DATA LIST
IMR02E20-E1
48
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
88
Decimal point
position
XU CH1
CH64
19EC
1A2B
6636
6699
7 R/W
C 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC input:
K, J, T, E:
Only 0 or 1 can be set.
R, S, B, N, PLII, W5Re/W26Re:
Only 0 can be set.
RTD input:
Only 0 or 1 can be set.
Voltage (V)/Current (I) inputs:
From 0 to 4 can be set.
Based on
model code
When not
specifying:
TC/RTD: 1
V/I: 1
89
Input scale high
XV
CH1
CH64
1A2C
1A6B
6700
6763
7 R/W
C TC/RTD inputs:
Input scale low to
Maximum value of the
selected
input
range
Voltage (V)/Current (I) inputs:
19999 to
19999
(However, a span is 20000 or
less.)
Varies with the setting of the decimal point
position.
TC/RTD:
Maximum
value of the
selected
input range
V/I: 100.0
90
Input scale low
XW
CH1
CH64
1A6C
1AAB
6764
6827
7 R/W
C TC/RTD inputs:
Minimum value of the selected
input range to Input scale high
Voltage (V)/Current (I) inputs:
19999 to
19999
(However, a span is 20000 or
less.)
Varies with the setting of the decimal point
position.
TC/RTD:
Minimum
value of the
selected
input range
V/I: 0.0
91
Input error
determination point
(high)
AV CH1
CH64
1AAC
1AEB
6828
6891
7 R/W
C Input error determination point
(low limit) to
(Input range high
5 % of Input
span)
Varies with the setting of the decimal point
position.
Input range
high
(5 %
of Input span)
92
Input error
determination point
(low)
AW
CH1
CH64
1AEC
1B2B
6892
6955
7 R/W
C (Input range low
5 % of Input
span) to
Input error determination point
(high limit)
Varies with the setting of the decimal point
position.
Input range
low
(5 %
of Input span)
93 Burnout
direction
BS CH1
CH64
1B2C
1B6B
6956
7019
1 R/W
C 0: Upscale
1: Downscale
Valid only when the TC input and voltage
(low) input are selected.
0
94
Square root extraction
XH
CH1
CH64
1B6C
1BAB
7020
7083
1 R/W
C 0: Unused
1: Used
0
95 Output
assignment
(Logic output
selection function)
E0 CH1
CH64
1BAC
1BEB
7084
7147
1 R/W
C 0: Control output
1: Logic output result
2: FAIL output
0
96
Energized/
De-energized
(Logic output
selection function)
NA CH1
CH64
1BEC
1C2B
7148
7211
1 R/W
C 0: Energized
1: De-energized
0