8. COMMUNICATION DATA LIST
IMR02E20-E1
45
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
59
RS ratio *
RR CH1
CH64
109C
10DB
4252
4315
7
R/W
C
0.001 to 9.999
1.000
60
Output distribution
selection
DV CH1
CH64
10DC
111B
4316
4379
1 R/W
C 0: Control output
1: Distribution output
0
61
Output distribution
bias
DW
CH1
CH64
111C
115B
4380
4443
7 R/W
C
100.0 to
100.0 %
0.0
62
Output distribution
ratio
DQ CH1
CH64
115C
119B
4444
4507
7 R/W
C
9.999 to
9.999 1.000
63
Proportional cycle
time
T0 CH1
CH64
119C
11DB
4508
4571
7 R/W
C 0.1 to 100.0 seconds
This item becomes RO (Only reading
data is possible) for the Voltage/Current
output specification.
This parameter is valid when “0: Control
output” has been selected at No.95
“Output assignment.”
Relay contact
output:
20.0
Voltage pulse
output, triac
output and
open collector
output: 2.0
64
Minimum ON/OFF
time of proportioning
cycle
VI CH1
CH64
11DC
121B
4572
4635
7 R/W
C 0 to 1000 ms
This item becomes RO (Only reading
data is possible) for the Voltage/Current
output specification.
0
65
Manual manipulated
output value
ON CH1
CH64
121C
125B
4636
4699
7 R/W
C PID control:
Output limiter low to
Output limiter high
Heat/Cool PID control:
Cool-side output limiter (high)
to
Heat-side output limiter
(high)
Position proportioning PID control:
When there is feedback resistance
(FBR) input and it does not break:
Output limiter low to
Output limiter high
When there is no feedback
resistance (FBR) input or the
feedback resistance (FBR) input is
disconnected:
0:
Close-side
output
OFF,
Open-side
output
OFF
1:
Close-side
output
ON,
Open-side
output
OFF
2:
Close-side
output
OFF,
Open-side
output
ON
0.0
66
Area soak time stop
function
RV CH1
CH64
125C
129B
4700
4763
1 R/W
C 0: No function
1: Event 1
2: Event 2
3: Event 3
4: Event 4
0
67
EDS mode
(for disturbance 1)
NG
CH1
CH64
129C
12DB
4764
4827
1 R/W
C 0: No function
1: EDS function mode
2: Learning mode
3: Tuning mode
EDS function: External disturbance
suppression
function
0
68
EDS mode
(for disturbance 2)
NX
CH1
CH64
12DC
131B
4828
4891
1 R/W
C
0
* When the cascade control is selected, this is used as the cascade ratio. When the ratio setting is selected, this is used as the ratio setting ratio.
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO modules
are unused.