8. COMMUNICATION DATA LIST
IMR02E20-E1
56
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
136 Undershoot
suppression factor
KB CH1
CH64
25EC
262B
9708
9771
7 R/W
C 0.000 to 1.000
Water cooling:
0.100
Air cooling:
0.250
Cooling gain
linear type:
1.000
137 Derivative gain
DG CH1
CH64
262C
266B
9772
9835
7 R/W
C 0.1 to 10.0
6.0
138 ON/OFF action
differential gap
(upper)
IV CH1
CH64
266C
26AB
9836
9899
7 R/W
C TC/RTD inputs:
0 (0.0) to Input span
(Unit:
C [
F])
Varies with the setting of the
decimal point position.
Voltage (V)/Current (I) inputs:
0.0 to 100.0 % of input span
TC/RTD: 1
V/I: 0.1
139 ON/OFF action
differential gap
(lower)
IW CH1
CH64
26AC
26EB
9900
9963
7 R/W
C
TC/RTD: 1
V/I: 0.1
140 Action (high) at input
error
WH
CH1
CH64
26EC
272B
9964
10027
1 R/W
C 0: Normal control
1: Manipulated output value at
Input
error
0
141 Action (low) at input
error
WL
CH1
CH64
272C
276B
10028
10091
1 R/W
C 0
142 Manipulated output
value at input error
OE CH1
CH64
276C
27AB
10092
10155
7 R/W
C
105.0 to
105.0 %
Actual output values become those
restricted by the output limiter.
Position proportioning PID control:
If there is no feedback resistance (FBR)
input or the feedback resistance (FBR)
input is disconnected, an action taken
when abnormal is in accordance with
the value action setting during STOP.
0.0
143 Manipulated output
value at STOP mode
[heat-side]
OF CH1
CH64
27AC
27EB
10156
10219
7 R/W
C
5.0 to
105.0 %
Position proportioning PID control:
Only when there is feedback resistance
(FBR) input and it does not break, the
manipulated output value [heat-side] at
STOP is output.
5.0
144 Manipulated output
value at STOP mode
[cool-side]
OG CH1
CH64
27EC
282B
10220
10283
7 R/W
C
5.0
145 Output change rate
limiter (up)
[heat-side]
PH CH1
CH64
282C
286B
10284
10347
7 R/W
C 0.0 to 100.0 % of manipulated
output/seconds
(0.0: OFF)
Becomes invalid when in Position
proportioning PID control.
0.0
146 Output change rate
limiter (down)
[heat-side]
PL CH1
CH64
286C
28AB
10348
10411
7 R/W
C
0.0
147 Output limiter (high)
[heat-side]
OH CH1
CH64
28AC
28EB
10412
10475
7 R/W
C Output limiter (low) to 105.0 %
Position proportioning PID control:
Becomes valid only when there is
feedback resistance (FBR) input and it
does not break.
105.0
148 Output limiter (low)
[heat-side]
OL CH1
CH64
28EC
292B
10476
10539
7 R/W
C
5.0 % to Output limiter (high)
Position proportioning PID control:
Becomes valid only when there is
feedback resistance (FBR) input and it
does not break.
5.0
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.