3. MOUNTING
IMR02E20-E1
8
Space required between each module vertically
When the module is mounted on the panel,
allow a minimum of 50 mm at the top and
bottom of the module to attach the module to
the mainframe.
Depth for modular cables mount type module
Space for modular cables must be considered
when installing.
It is recommended to use a plastic cover on the connector on both sides of the mounted modules
for protection of connectors.
Joint connector cover
Be sure the COM-ML and SRZ function modules (Z-TIO, Z-DIO and Z-CT modules) are joined
when using them.
(5)
In case this instrument is connected to a supply by means of a permanent connection, a switch or
circuit-breaker shall be included in the installation. This shall be in close proximity to the
equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the
equipment.
50 mm or more
COM
76.9 mm
Communication
cable
Approx.
50 mm