APPENDIX. HOST COMMUNICATION PROTOCOL
IMR02E20-E1
119
(3) Data sent from the host computer
The host computer sends data for the selecting sequence with the following format:
When no memory area number is specified
When the memory area number is specified
For the STX, Memory area number Identifier, Data, ETB, ETX and BCC, refer to
A.2.1 Polling
procedures (P. 112)
.
If the length of send data (from STX to BCC) exceeds 136 bytes, it is divided into blocks by
ETB. In this case, the succeeding divided data is sent after STX.
Area soak time set data as the following:
When data range is 0 hour 00 minute to 99 hours 59 minutes:
Data range is 0:00 to 99:59, punctuation of time unit is expressed in colon “: (3AH).”
When data range is 0 hour 00 minute to 99 hours 59 minutes:
Data range is 0:00 to 99:59, punctuation of time unit is expressed in colon “: (3AH).”
In addition to above, when minute and second data are set in more than 60, become as the
following:
Example: 1:65 (1 hour 65 minutes)
→
2:05 (2 hours 05 minutes)
0:65 (0 minute 65 seconds)
→
1:05 (1 minute 05 seconds)
Identifier Data
BCC
ETB
STX
Identifier Data
BCC
ETX
STX
or
Data
BCC
ETB
STX
Data
BCC
ETX
STX
or
Identifier
Identifier
Memory
area
number
Memory
area
number