8. COMMUNICATION DATA LIST
IMR02E20-E1
51
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
105 Event 2
channel setting
FB CH1
CH64
1E2C
1E6B
7724
7787
1 R/W
C 1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
This function is valid when “deviation
between channels” is selected.
1
106 Event 2 hold action
WB
CH1
CH64
1E6C
1EAB
7788
7851
1 R/W
C 0: OFF
1: Hold action ON (when power turned
on; when transferred from STOP to
RUN)
2: Re-hold action ON (when power
turned on; when transferred from
STOP to RUN; SV changed)
This function is valid when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in remote mode and
while setting changing rate limiter is
working.
Based on
model code
When not
specifying:
0
107 Event 2 interlock
LG CH1
CH64
1EAC
1EEB
7852
7915
1 R/W
C 0: Unused
1: Used
0
108 Event 2
differential gap
HB CH1
CH64
1EEC
1F2B
7916
7979
7 R/W
C
Deviation, process, set value, or
Deviation action between channels:
0 (0.0) to Input span (Unit:
C [
F])
Varies with the setting of the
decimal point position.
MV: 0.0 to 110.0 %
: 1
: 1.0
109 Event 2 delay timer
TG CH1
CH64
1F2C
1F6B
7980
8043
7
R/W
C
0 to 18000 seconds
0
110 Force ON of Event 2
action
OB CH1
CH64
1F6C
1FAB
8044
8107
7 R/W
C
RKC communication
Least significant digit:
Event output turned on at input
error occurrence
2nd digit:
Event output turned on in manual
mode
3rd digit:
Event output turned on during the
Autotuning (AT) function is being
executed
4th digit:
Event output turned on during the
setting change rate limiter is being
operated
5th digit to Most significant digit:
Unused
Data 0: Invalid
1: Valid
Modbus
Bit data
Bit 0: Event output turned on at
input error occurrence
Bit 1: Event output turned on in
manual
mode
Bit 2: Event output turned on
during the Autotuning (AT)
function is being executed
Bit 3: Event output turned on
during the setting change
rate limiter is being operated
Bit 4 to Bit 15: Unused
Data 0: Invalid
1: Valid
[Decimal number: 0 to 15]
0