6. COMMUNICATION SETTING OF FUNCTION MODULE
IMR02E20-E1
24
Address setting example of function module (16 Z-TIO modules, 7 Z-DIO modules and
7 Z-CT modules):
Z-TIO module
(16 modules)
0
Z-DIO module
(7 modules)
1
6
F 0
6
0
Z-CT module
(7 modules)
Module
address
setting
6.2 Temperature Control Channel of the SRZ Unit
Setting the Z-TIO module address determines the temperature control channel number used for
communication. To each Z-TIO module address, the relevant temperature control channel is assigned.
Each temperature control channel number can be calculated from the following equation.
Temperature control channel number of communication
[Module address setting
a
]
[Maximum channel number of the function module
b
]
+ [Channel number in a module]
a
When the setting is A to F, it is a decimal number.
b
For the Z-TIO module, it is calculated by “4.”
Example: When 16 Z-TIO modules (4-channel type) are joined
Module address setting
0
1
2
Z-TIO module 1
Z-TIO module 3
Z-TIO module 2
CH1
CH2
CH3
CH4
CH9
CH10
CH11
CH12
CH5
CH6
CH7
CH8
F
Z-TIO module 16
CH61
CH62
CH63
CH64
Z-TIO module 3: The temperature control channel number used for communication of channel 4
2
4 + 4
12