APPENDIX. HOST COMMUNICATION PROTOCOL
IMR02E20-E1
137
[Example 1] When data on the Event 1 set value in Memory area 2 of CH1 is read
1.
The memory area number, “2” is written to the CH1 setting memory area number (386CH).
Data in Memory area 2 is called up to the CH1 register addresses.
CH1 register addresses
Setting memory area number
386CH
2
Memory area number “2”
Event 1 set value (EV1)
38ACH
50
Event 2 set value (EV2)
38ECH
Event 3 set value (EV3)
392CH
Event 4 set value (EV4)
396CH
Control loop break alarm (LBA) time
39ACH
LBA deadband
39ECH
Set value (SV)
3A2CH
Proportional band [heat-side]
3A6CH
Integral time [heat-side]
3AACH
Derivative time [heat-side]
3AECH
The data of memory area 2 is loaded into these register addresses.
Control response parameter
3B2CH
Proportional band [cool-side]
3B6CH
Integral time [cool-side]
3BACH
Derivative time [cool-side]
3BECH
Overlap/Deadband 3C2CH
Manual reset
3C6CH
Setting change rate limiter (up)
3CACH
Setting change rate limiter (down)
3CECH
Area soak time
3D2CH
Link area number 3D6CH
2.
Data “50” on Event 1 set value (38ACH) is read.
[Example 2] When the set value (SV) in Memory area 3 of CH1 is changed to 200
1.
The memory area number, “3” is written to the CH1 setting memory area number (386CH).
Data in Memory area 3 is called up to the CH1 register addresses.
CH1 register addresses
Setting memory area number
386CH
3
Memory area number “3”
Event 1 set value (EV1)
38ACH
Event 2 set value (EV2)
38ECH
Event 3 set value (EV3)
392CH
Event 4 set value (EV4)
396CH
Control loop break alarm (LBA) time
39ACH
LBA deadband
39ECH
Set value (SV)
3A2CH
150
Proportional band [heat-side]
3A6CH
Integral time [heat-side]
3AACH
Derivative time [heat-side]
3AECH
The data of memory area 3 is loaded into these register addresses.
Control response parameter
3B2CH
Proportional band [cool-side]
3B6CH
Integral time [cool-side]
3BACH
Derivative time [cool-side]
3BECH
Overlap/Deadband 3C2CH
Manual reset
3C6CH
Setting change rate limiter (up)
3CACH
Setting change rate limiter (down)
3CECH
Area soak time
3D2CH
Link area number 3D6CH
2.
“200” is written to the set value (SV) (3A2CH).