8. COMMUNICATION DATA LIST
IMR02E20-E1
63
Continued from the previous page.
No
.
Name
Chan-
nel
Register address Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
14
Integral time [cool-side]
CH1
CH64
3BAC
3BEB
15276
15339
R/W
C
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action)
240
15
Derivative time
[cool-side]
CH1
CH64
3BEC
3C2B
15340
15403
R/W
C
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
60
16 Overlap/Deadband
CH1
CH64
3C2C
3C6B
15404
15467
R/W
C
TC/RTD inputs:
Input span to +Input span (Unit:
C [
F])
Varies with the setting of the decimal point
position.
Voltage (V)/Current (I) inputs:
100.0 to
100.0 % of input span
0 (0.0)
17 Manual
reset
CH1
CH64
3C6C
3CAB
15468
15531
R/W
C
100.0 to
100.0 %
0.0
18
Setting change rate limiter
(up)
CH1
CH64
3CAC
3CEB
15532
15595
R/W
C
0 (0.0) to Input span/unit time *
0 (0.0): Unused
Varies with the setting of the decimal point position.
0 (0.0)
19
Setting change rate limiter
(down)
CH1
CH64
3CEC
3D2B
15596
15659
R/W
C
* Unit time: 60 seconds (factory set value)
0 (0.0)
20
Area soak time
CH1
CH64
3D2C
3D6B
15660
15723
R/W
C
0 minutes 00 seconds to 199 minutes 59 seconds:
0 to 11999 seconds
0 hours 00 minutes to 99 hours 59 minutes:
0 to 5999 minutes
0
21
Link area number
CH1
CH64
3D6C
3DAB
15724
15787
R/W
C
0 to 8
(0: No link)
0
22
Unused
3DAC
3E6B
15788
15979