4. WIRING
IMR02E20-E1
20
4.4.3 Connections for loader communication
Connect a USB communication converter COM-K2 (sold separately)* between the personal computer
and the COM-ML.
Loader communication makes it possible to check and set data of the COM-ML and the controller
(SRZ).
*
A loader communication cable (optional) is required for the connection to the loader communication
connector on the COM-ML.
USB communication converter COM-K2-1 (with Loader communication cable [cable length: 1.5 m])
During the loader communication, the COM-ML requires an external power source. The
COM-ML will not function on the USB power from a personal computer alone.
The module address for loader communication is fixed at “0.”
Loader communication corresponds to RKC communication (based on ANSI X3.28-1976
subcategories 2.5 and B1).
When using the loader communication, USB driver for COM-K2 must be installed on the
personal computer.
The USB driver for COM-K2 can be downloaded the official RKC website:
http://www.rkcinst.com
For the COM-K2, refer to the
COM-K2 Instruction Manual (IMR01Z02-E
)
.
Personal
computer
USB communication
converter COM-K2
(RKC product)
Connect to USB
port of a personal
computer
Connect to
USB connecter
of COM-K2
The termination
resistor is built
into the COM-K2.
Loader
communication cable
(W-BV-01)
[Optional]
Connect to loader
communication
connector of COM-ML
Connect to loader
communication
connector
USB cable
(COM-K2 accessory)
Communication settings on the
computer
(the following settings are all fixed)
Communication speed: 38400 bps
Start bit:
1
Data bit:
8
Parity bit:
Without
Stop bit:
1