11. SPECIFICATIONS
IMR02E20-E1
108
Loader communication
Connection method:
Connection with a loader communication cable for our USB converter
COM-K2 (sold separately).
Protocol:
RKC communication (ANSI X3.28-1976 subcategories 2.5 and B1)
Synchronous method:
Start/Stop synchronous type
Communication speed:
38400
bps
Data bit configuration:
Start
bit:
1
Data bit: 8
Parity bit: Without
Stop bit: 1
Maximum connections:
One SRZ unit
Self-diagnostic function
Major fault
Action stop:
RAM value abnormal
Power supply voltage monitoring error
Watchdog timer error
Instrument status:
Display: A red lamp (FAIL/RUN) is on
Host communication:
Receive
mode
Network communication:
Receive
mode
Error recovery:
Recovery by device power restart after cause of error is removed
Recoverable fault
Data back-up error:
Display: A green lamp (FAIL/RUN) frashes
Status: Error code 2
Stack overflow:
Display: A green lamp (FAIL/RUN) frashes
Status: Error code 64
Network module error:
Display: A green lamp (FAIL/RUN) frashes
Status: Error code 512