7. INITIAL COMMUNICATION DATA SETTINGS
IMR02E20-E1
33
Setting example (
The condition is the same as the setting example on Page 29.)
When one Z-TIO module is connected to the COM-ML, set the following conditions.
Use the Measured value (PV) and the Set value (SV) [CH1 to CH4] of the Z-TIO module.
Communication data items setting:
Measured value (PV), Set value (SV)
Number of measured data items (IN): Measured value (PV): 4
Set value (SV): 4
Number of setting data items (OUT): Set value (SV): 4
Make setting of “Communication data items setting,” “Number of measured data items (IN),”
and “Number of setting data items (OUT)” through the host communication or through the
loader communication.
Content of each module of PROFINET communication
Slot 1
IN_001:
Read out value of the Measured value (PV) CH1
IN_002:
Read out value of the Measured value (PV) CH2
IN_003:
Read out value of the Measured value (PV) CH3
IN_004:
Read out value of the Measured value (PV) CH4
IN_005:
Read out value of the Set value (SV) CH1
IN_006:
Read out value of the Set value (SV) CH2
IN_007:
Read out value of the Set value (SV) CH3
IN_008:
Read out value of the Set value (SV) CH4
Slot 1 to 8 IN_009 to 128: 0
Slot 9
Write_permission: Setting state selection
Set Bit 0 to “1” to write data.
Slot 10
OUT_001:
The written value of the set value (SV) CH1
OUT_002:
The written value of the set value (SV) CH2
OUT_003:
The written value of the set value (SV) CH3
OUT_004:
The written value of the set value (SV) CH4
Slot 10 to 17 OUT_005 to 127: Invalid writing