8. COMMUNICATION DATA LIST
IMR02E20-E1
64
8.5 Communication Data of Z-DIO Module
For details of Z-DIO module communication data, refer to
SRZ Instruction Manual
(IMS01T04-E
)
.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
1
Digital input (DI)
state 1
L1 CH1
CH16
3E6C
3E7B
15980
15995
7 RO
M
RKC communication
Least significant digit: DI1
2nd digit:
DI2
3rd digit:
DI3
4th digit:
DI4
5th digit to Most significant digit:
Unused
Data 0: Contact open
1: Contact closed
Modbus
Bit data
Bit 0: DI1
Bit 1: DI2
Bit 2: DI3
Bit 3: DI4
Bit 4: DI5
Bit 5: DI6
Bit 6: DI7
Bit 7: DI8
Bit 8 to Bit 15: Unused
Data 0: Contact open
1: Contact closed
[Decimal number: 0 to 255]
2
Digital input (DI)
state 2
L6 CH1
CH16
7
RO
M
RKC communication
Least significant digit: DI5
2nd digit:
DI6
3rd digit:
DI7
4th digit:
DI8
5th digit to Most significant digit:
Unused
Data 0: Contact open
1: Contact closed
3
Digital output (DO)
state 1
Q2 CH1
CH16
3E7C
3E8B
15996
16011
7 RO
M
RKC communication
Least significant digit: DO1
2nd digit:
DO2
3rd digit:
DO3
4th digit:
DO4
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: DO1
Bit 1: DO2
Bit 2: DO3
Bit 3: DO4
Bit 4: DO5
Bit 5: DO6
Bit 6: DO7
Bit 7: DO8
Bit 8 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 255]
4
Digital output (DO)
state 2
Q3 CH1
CH16
7
RO
M
RKC communication
Least significant digit: DO5
2nd digit:
DO6
3rd digit:
DO7
4th digit:
DO8
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
Continued on the next page.