8. COMMUNICATION DATA LIST
IMR02E20-E1
41
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
18
Unused
05DC
05EB
1500
1515
19
Holding peak value
ambient temperature
monitor
Hp CH1
CH64
05EC
062B
1516
1579
7 RO
C
10.0 to
100.0
C
(14.0 to 212.0
F)
20
Unused
062C
063B
1580
1595
21
Logic output
monitor 1
ED CH1
CH16
063C
064B
1596
1611
7 RO
M
RKC communication
Least significant digit:
Logic output 1
2nd digit: Logic output 2
3rd digit: Logic output 3
4th digit: Logic output 4
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: Logic output 1
Bit 1: Logic output 2
Bit 2: Logic output 3
Bit 3: Logic output 4
Bit 4: Logic output 5
Bit 5: Logic output 6
Bit 6: Logic output 7
Bit 7: Logic output 8
Bit 8 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 255]
22
Logic output
monitor 2
EE CH1
CH16
7
RO
M
Least significant digit:
Logic output 5
2nd digit: Logic output 6
3rd digit: Logic output 7
4th digit: Logic output 8
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
23
Unused
064C
080B
1612
2059
24 PID/AT
transfer
G1 CH1
CH64
080C
084B
2060
2123
1 R/W
C 0: PID control
1: Autotuning (AT) *
* Automatically reverts to 0 after
autotuning ends.
0
25 Auto/Manual
transfer J1 CH1
CH64
084C
088B
2124
2187
1 R/W
C 0: Auto mode
1: Manual mode
0
26 Remote/Local
transfer C1 CH1
CH64
088C
08CB
2188
2251
1 R/W
C 0: Local mode
1: Remote mode
When performing remote control by
remote setting input and also performing
cascade control and ratio setting,
transfer to the Remote mode.
0
27
Unused
08CC
08DB
2252
2267
28
Memory area transfer
ZA
CH1
CH64
08DC
091B
2268
2331
7
R/W
C
1 to 8
1
Continued on the next page.