8. COMMUNICATION DATA LIST
IMR02E20-E1
55
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
125 CT
ratio
XS CH1
CH64
232C
236B
9004
9067
7
R/W
C
0 to 9999
CTL-6-P-N:
800
CTL-12-S56-
10L-N:
1000
126 CT
assignment
ZF
CH1
CH64
236C
23AB
9068
9131
1 R/W
C 0: None
1: OUT1
2: OUT2
3: OUT3
4: OUT4
CH1: 1, CH2: 2
CH3: 3, CH4: 4
(for each
Z-TIO module)
127 Heater break alarm
(HBA) type
ND CH1
CH64
23AC
23EB
9132
9195
1 R/W
C 0: Heater break alarm (HBA)
type A (Time-proportional
control
output)
1: Heater break alarm (HBA)
type B (Continuous control
output)
Set value is
based on the
Output type
specified at
ordering.
128 Number of heater
break alarm (HBA)
delay times
DH CH1
CH64
23EC
242B
9196
9259
7 R/W
C 0 to 255 times
5
129 Hot/Cold start
XN CH1
CH64
242C
246B
9260
9323
1 R/W
C 0: Hot start 1
1: Hot start 2
2: Cold start
0
130 Start determination
point
SX CH1
CH64
246C
24AB
9324
9387
7 R/W
C 0 (0.0) to Input span
(The unit is the same as input value.)
0 (0.0): Action depending on the
Hot/Cold start selection
Varies with the setting of the
decimal point position.
Based on
specification
131 SV tracking
XL CH1
CH64
24AC
24EB
9388
9451
1 R/W
C 0: Unused
1: Used
1
132 MV transfer function
[Action taken when
changed to Manual mode
from Auto mode]
OT CH1
CH64
24EC
252B
9452
9515
1 R/W
C 0: MV in Auto mode is used.
[Balanceless-bumpless function]
1: MV in previous Manual mode is
used.
0
133 Control
action
XE CH1
CH64
252C
256B
9516
9579
1 R/W
C 0: Brilliant II PID control
(Direct
action)
1: Brilliant II PID control
(Reverse
action)
2: Brilliant II Heat/Cool PID
control [Water cooling type]
3: Brilliant II Heat/Cool PID
control [Air cooling type]
4: Brilliant II Heat/Cool PID
control [Cooling gain linear type]
5: Brilliant II position proportioning
PID
control
Odd channel: From 0 to 5 can be set.
Even channel: Only 0 or 1 can be set. *
* In Heat/Cool PID control and Position
proportioning PID control, control
action is not performed. Only PV
monitor and event action is performed.
Based on
model code
When not
specifying: 1
134 Integral/Derivative
time decimal point
position
PK CH1
CH64
256C
25AB
9580
9643
1 R/W
C 0: 1 second setting
(No decimal place)
1: 0.1 seconds setting
(One decimal place)
0
135 Derivative
action
KA CH1
CH64
25AC
25EB
9644
9707
1 R/W
C 0: Measured value derivative
1: Deviation derivative
0
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Continued on the next page.