8. COMMUNICATION DATA LIST
IMR02E20-E1
43
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
40
Control response
parameter
★
CA
CH1
CH64
0BDC
0C1B
3036
3099
1 R/W
C 0: Slow
1: Medium
2: Fast
When the P or PD action is selected, this
setting becomes invalid.
PID control,
Position
proportioning
PID control: 0
Heat/Cool PID
control: 2
41
Proportional band
[cool-side]
★
P2 CH1
CH64
0C1C
0C5B
3100
3163
7 R/W
C TC/RTD inputs:
1 (0.1) to Input span
(Unit:
C [
F])
Varies with the setting of the decimal
point position selection.
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of input span
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
TC/RTD:
30 (30.0)
V/I: 30.0
42
Integral time
[cool-side]
★
I2 CH1
CH64
0C5C
0C9B
3164
3227
7 R/W
C 0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PD action)
Varies with the setting of the Integral/
Derivative time decimal point position
selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
240
43
Derivative time
[cool-side]
★
D2
CH1
CH64
0C9C
0CDB
3228
3291
7 R/W
C 0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the Integral/
Derivative time decimal point position
selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
60
44
Overlap/Deadband
★
V1
CH1
CH64
0CDC
0D1B
3292
3355
7 R/W
C TC/RTD inputs:
Input span to +Input span
(Unit:
C [
F])
Voltage (V)/current (I) inputs:
100.0 to +100.0 % of input span
Minus (
) setting results in overlap.
However, the overlapping range is
within the proportional range.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
0 (0.0)
45 Manual
reset
★
MR
CH1
CH64
0D1C
0D5B
3356
3419
7 R/W
C
100.0 to +100.0 %
If the integral function is valid, set to
RO (Only reading data is possible).
When integral action (heating or cooling
side) is zero, manual reset value is
added to the control output.
0.0
46
Setting change rate
limiter (up)
★
HH
CH1
CH64
0D5C
0D9B
3420
3483
7 R/W
C 0 (0.0) to Input span/unit time *
0 (0.0): Unused
0 (0.0)
47
Setting change rate
limiter (down)
★
HL
CH1
CH64
0D9C
0DDB
3484
3547
7 R/W
C
* Unit time: 60 seconds
(factory set value)
0 (0.0)
★
Parameters which can be used in multi-memory area function
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Continued on the next page.