8. COMMUNICATION DATA LIST
IMR02E20-E1
47
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
84
Communication
switch for logic
EF CH1
CH16
16DC
16EB
5852
5867
7 R/W
M
RKC communication
Least significant digit:
Communication switch 1
2nd digit: Communication switch 2
3rd digit: Communication switch 3
4th digit: Communication switch 4
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: Communication switch 1
Bit 1: Communication switch 2
Bit 2: Communication switch 3
Bit 3: Communication switch 4
Bit 4 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 15]
0
85
Unused
16EC
196B
5868
6507
Set data No. 86 or later are for engineering setting [Writable in the STOP mode]
86
Input type
XI
CH1
CH64
196C
19AB
6508
6571
7 R/W
C 0: TC input K
1: TC input J
2: TC input R
3: TC input S
4: TC input B
5: TC input E
6: TC input N
7: TC input T
8: TC input W5Re/W26Re
9: TC input PLII
12: RTD input Pt100
13: RTD input JPt100
14: Current input 0 to 20 mA DC
15: Current input 4 to 20 mA DC
16: Voltage (high) input
0 to 10 V DC
17: Voltage (high) input
0 to 5 V DC
18: Voltage (high) input
1 to 5 V DC
19: Voltage (low) input
0 to 1 V DC
20: Voltage (low) input
0 to 100 mV DC
21: Voltage (low) input
0 to 10 mV DC
22: Feedback resistance input
100 to 150
23: Feedback resistance input
151
to 6 k
If changed to Voltage (high) input from
TC/RTD/Current/Voltage (low)/
Feedback resistance input, select the
hardware by the input selector switch at
the side of the module.
Refer to
SRZ Instruction Manual
(IMS01T04-E
)
.
Based on
model code
When not
specifying: 0
87
Display unit
PU CH1
CH64
19AC
19EB
6572
6635
7 R/W
C
0:
C
1:
F
Use to select the temperature unit for
thermocouple (TC) and RTD inputs.
Based on
model code
When not
specifying: 0
Continued on the next page.