8. COMMUNICATION DATA LIST
IMR02E20-E1
39
8.3 Communication Data of Z-TIO Module
For details of Z-TIO module communication data, refer to
SRZ Instruction Manual
(IMS01T04-E
)
.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
1 Measured
value
(PV)
M1 CH1
CH64
01FC
023B
508
571
7
RO
C
Input scale low to Input scale high
2
Comprehensive
event state
AJ CH1
CH64
023C
027B
572
635
7 RO
C
RKC communication
Least significant digit:
Event
1
2nd digit: Event 2
3rd digit: Event 3
4th digit: Event 4
5th digit: Heater break alarm (HBA)
6th digit: Temperature rise
completion
7th digit: Burnout
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: Event 1
Bit 1: Event 2
Bit 2: Event 3
Bit 3: Event 4
Bit 4: Heater break alarm (HBA)
Bit 5: Temperature rise completion
Bit 6: Burnout
Bit 7 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 127]
3
Operation mode
state monitor
L0 CH1
CH64
027C
02BB
636
699
7 RO
C
RKC communication
Least significant digit:
STOP
(Control
STOP)
2nd digit: Control RUN (Control start)
3rd digit: Manual mode
4th digit: Remote mode
5th digit to Most significant digit:
Unused
Data 0: OFF
1: ON
Modbus
Bit data
Bit 0: Control STOP (Control STOP)
Bit 1: Control RUN (Control start)
Bit 2: Manual mode
Bit 3: Remote mode
Bit 4 to Bit 15: Unused
Data 0: OFF
1: ON
[Decimal number: 0 to 15]
4
Unused
02BC
02CB
700
715
5
Manipulated output
value (MV) monitor
[heat-side]
O1 CH1
CH64
02CC
030B
716
779
7 RO
C PID control or Heat/Cool PID control:
5.0 to
105.0 %
Position proportioning PID control
with feedback resistance (FBR) input:
0.0 to 100.0 %
6
Manipulated output
value (MV) monitor
[cool-side]
O2 CH1
CH64
030C
034B
780
843
7 RO
C
5.0 to
105.0 %
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Continued on the next page.