8. COMMUNICATION DATA LIST
IMR02E20-E1
59
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
176 Open/Close
output
neutral zone
V2 CH1
CH64
2FEC
302B
12268
12331
7 R/W
C 0.1 to 10.0 % of output
2.0
177 Action at feedback
resistance (FBR) input
error
SY CH1
CH64
302C
306B
12332
12395
1 R/W
C 0: Action depending on the valve
action at STOP
1: Control action continued
0
178 Feedback
adjustment
FV CH1
CH64
306C
30AB
12396
12459
1 R/W
C 0: Adjustment end
1: Open-side adjustment start
2: Close-side adjustment start
179 Control
motor
time
TN CH1
CH64
30AC
30EB
12460
12523
7 R/W
C 5 to 1000 seconds
10
180 Integrated
output
limiter
OI CH1
CH64
30EC
312B
12524
12587
7 R/W
C 0.0 to 200.0 % of control motor time
(0.0: OFF)
Becomes invalid when there is feedback
resistance (FBR) input.
150.0
181 Valve action at STOP
VS CH1
CH64
312C
316B
12588
12651
1 R/W
C 0: Close-side output OFF,
Open-side
output
OFF
1: Close-side output ON,
Open-side
output
OFF
2: Close-side output OFF,
Open-side
output
ON
Becomes valid when there is no feedback
resistance (FBR) input or the feedback
resistance (FBR) input is disconnected.
0
182 ST proportional band
adjusting factor
KI CH1
CH64
316C
31AB
12652
12715
7 R/W
C 0.01 to 10.00 times
1.00
183 ST integral time
adjusting factor
KJ CH1
CH64
31AC
31EB
12716
12779
7 R/W
C 0.01 to 10.00 times
1.00
184 ST derivative time
adjusting factor
KK CH1
CH64
31EC
322B
12780
12843
7 R/W
C 0.01 to 10.00 times
1.00
185 ST start condition
SU CH1
CH64
322C
326B
12844
12907
1 R/W
C 0: Activate the Startup tuning (ST)
function when the power is
turned on; when transferred
from STOP to RUN; or when
the Set value (SV) is changed.
1: Activate the Startup tuning (ST)
function when the power is
turned on; or when transferred
from STOP to RUN.
2: Activate the Startup tuning (ST)
function when theSet value (SV)
is changed.
0
186 Automatic
temperature
rise group
Y7 CH1
CH64
326C
32AB
12908
12971
7 R/W
C 0 to 16
(0: Automatic temperature rise
function
OFF)
0
187 Automatic
temperature
rise dead time
RT CH1
CH64
32AC
32EB
12972
13035
7 R/W
C 0.1 to 1999.9 seconds
10.0
188 Automatic temperature
rise gradient data
R2 CH1
CH64
32EC
332B
13036
13099
7 R/W
C 0.1 to Input span/minutes
Varies with the setting of the decimal
point position.
1.0
Parameters only used for Heat/Cool PID control or Position proportioning PID control, therefore data for CH2 and CH4 of Z-TIO
modules are unused.
Continued on the next page.