8. COMMUNICATION DATA LIST
IMR02E20-E1
52
Continued from the previous page.
No.
Name
Iden-
tifier
Chan-
nel
Register address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX DEC
111 Event 3 type
XC
CH1
CH64
1FAC
1FEB
8108
8171
7 R/W
C 0: None
1: Deviation high
(Using SV monitor value)
1
2: Deviation low
(Using SV monitor value)
1
3: Deviation high/low
(Using SV monitor value)
1
4: Band (Using SV monitor value)
1
5: Process high
1
6: Process low
1
7: SV high
8: SV low
9: Unused
10: MV high [heat-side]
1,
2
11: MV low [heat-side]
1,
2
12: MV high [cool-side]
1
13: MV low [cool-side]
1
14: Deviation high
(Using local SV value)
1
15: Deviation low
(Using local SV value)
1
16: Deviation high/low
(Using local SV value)
1
17: Band (Using local SV value)
1
18: Deviation between channels high
1
19: Deviation between channels low
1
20: Deviation between channels
high/low
1
21: Deviation between channels
band
1
1
Event hold action is available.
2
If there is feedback resistance (FBR)
input in Position proportioning PID
control, set to the feedback resistance
(FBR) input value.
Based on
model code
When not
specifying:
0
112 Event
3
channel setting
FC CH1
CH64
1FEC
202B
8172
8235
1 R/W
C 1: Channel 1
2: Channel 2
3: Channel 3
4: Channel 4
This function is valid when “deviation
between channels” is selected.
1
113 Event 3 hold action
WC
CH1
CH64
202C
206B
8236
8299
1 R/W
C 0: OFF
1: Hold action ON (when power turned
on; when transferred from STOP to
RUN)
2: Re-hold action ON (when power
turned on; when transferred from
STOP to RUN; SV changed)
This function is valid when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in remote mode and
while setting changing rate limiter is
working.
Based on
model code
When not
specifying:
0
114 Event 3 interlock
LH CH1
CH64
206C
20AB
8300
8363
1 R/W
C 0: Unused
1: Used
0
115 Event
3
differential gap
HC CH1
CH64
20AC
20EB
8364
8427
7 R/W
C
Deviation, process, set value, or
Deviation action between channels:
0 (0.0) to Input span (Unit:
C [
F])
Varies with the setting of the
decimal point position.
MV: 0.0 to 110.0 %
: 1
: 1.0
116 Event 3 delay timer
TE CH1
CH64
20EC
212B
8428
8491
7
R/W
C
0 to 18000 seconds
If Event 3 corresponds to “9: Temperature
rise completion,” the Event 3 delay timer
becomes the temperature rise completion
soak time.
0
Continued on the next page.