8. COMMUNICATION DATA LIST
IMR02E20-E1
69
8.6 Communication Data of Z-CT Module
For details of Z-CT module communication data, refer to
Z-CT Instruction Manual [Detailed
version] (IMS01T21-E
)
.
No. Name
Iden-
tifier
Chan-
nel
Resister address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX
DEC
1
Current transformer
(CT) input value
monitor
M4 CH1
CH192
46BC
477B
18108
18299
7 RO
C CTL-6-P-Z:
0.0 to 10.0 A
CTL-6-P-N:
0.0 to 30.0 A
CTL-12-S56-10L-N: 0.0 to 100.0 A
2
Load factor
conversion
CT monitor
M5 CH1
CH192
477C
483B
18300
18491
7
RO
C
0.0 to 100.0 A
3
Heater break alarm
(HBA) state monitor
AF CH1
CH192
483C
48FB
18492
18683
1 RO
C 0: Normal
1: Break
2: Melting
4
Heater overcurrent
alarm state monitor
AG CH1
CH192
48FC
49BB
18684
18875
1 RO
C 0: Normal
1: Heater overcurrent
5
Automatic setting
state monitor
1
CJ
CH1
CH16
49BC
49CB
18876
18891
1 RO
M 0: Normal state
1: Automatic setting execution
2: Automatic setting failure
6
Unused
49CC
4FCB
18892
20427
7 Heater
break/Heater
overcurrent alarm
automatic setting
selection
BT
CH1
CH192
4FCC
508B
20428
20619
1
R/W
C
0: Automatic setting is disabled.
(Alarm set value cannot be
automatically set by the push
button and communication.)
1: Automatic setting for heater
break alarm (HBA) is enabled.
2: Automatic setting for heater
overcurrent alarm set value is
enabled.
3: Automatic setting for heater
break alarm (HBA) and heater
overcurrent alarm set values are
enabled.
1
8 Automatic
setting
transfer
2
BU
CH1
CH192
508C
514B
20620
20811
1 R/W
C 0:
Normal
state
1: Automatic setting execution
When automatic setting ends
normally, this reverts to
“0: Normal state.”
2: Automatic setting failure (RO)
0
9
Heater break alarm
(HBA) set value
A8
CH1
CH192
514C
520B
20812
21003
7
R/W
C
0.0 to 100.0 A
0.0: Heater break alarm function
(HBA) OFF
(HBA function OFF: The
current transformer (CT) input
value monitoring is available.)
0.0
10
Heater break alarm
(HBA) selection
BZ
CH1
CH192
520C
52CB
21004
21195
1
R/W
C
0: Heater break alarm (HBA)
unused
1: Heater break alarm (HBA)
2: Heater break alarm (HBA)
(With alarm interlock function)
1
1
This is linked to the solid lighting or blinking state of the automatic setting state indication lamp (SET).
2
Automatic setting is only possible for channels that have been set to other than “0: Automatic setting is disabled” in heater break/heater
overcurrent alarm automatic setting selection.
Continued on the next page.