8. COMMUNICATION DATA LIST
IMR02E20-E1
70
Continued from the previous page.
No. Name
Iden-
tifier
Chan-
nel
Resister address
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set value
HEX
DEC
11
Heater overcurrent
alarm set value
A6 CH1
CH192
52CC
538B
21196
21387
7 R/W
C 0.0 to 105.0 A
0.0: Heater overcurrent alarm
function
OFF
0.0
12
Heater overcurrent
alarm selection
BO CH1
CH192
538C
544B
21388
21579
1 R/W
C 0: Heater overcurrent alarm
unused
1: Heater overcurrent alarm
2: Heater overcurrent alarm
(With alarm interlock function)
1
13
Heater break alarm
(HBA) interlock
release
CX CH1
CH192
544C
550B
21580
21771
1 R/W
C 0: Normal state
1: Interlock release execution
After the interlock is released,
this automatically returns to “0.”
0
14
Heater overcurrent
alarm interlock
release
CY CH1
CH192
550C
55CB
21772
21963
1 R/W
C 0: Normal state
1: Interlock release execution
After the interlock is released,
this automatically returns to “0.”
0
15
Unused
55CC
5E0B
21964
24075
16 Set
lock
1
LK
CH1
CH16
5E0C
5E1B
24076
24091
1 R/W
M 0: Unlock
1: Lock
0
Set data No. 17 or later are for engineering setting [Writable in the STOP mode]
17 CT
type
2
BV
CH1
CH192
5E1C
5EDB
24092
24283
1 R/W
3
C
0: CTL-6-P-N (0.0 to 30.0 A)
1: CTL-12-S56-10L-N
(0.0 to 100.0 A)
2: CTL-6-P-Z (0.0 to 10.0 A)
Based on
model code.
When not
specifying:
0
18
CT ratio
4
(CT number of winds)
XT CH1
CH192
5EDC
5F9B
24284
24475
7 R/W
3
C
0 to 9999
CTL-6-P-N,
CTL-6-P-Z:
800
CTL-12-
S56-10L-N:
1000
19
Number of heater
break alarm (HBA)
delay times
DI CH1
CH192
5F9C
605B
24476
24667
7 R/W
3
C
0 to 255 times
5
20
Automatic setting
factor for heater break
alarm (HBA)
BW
CH1
CH192
605C
611B
24668
24859
7 R/W
3
C
1 to 100 %
75
21
Automatic setting
factor for heater
overcurrent alarm
B9 CH1
CH192
611C
61DB
24860
25051
7 R/W
3
C
100 to 1000 %
200
22
Determination current
value for automatic
setting
BP CH1
CH192
61DC
629B
25052
25243
7 R/W
3
C
0.0 to 100.0 A
1.0
23
Automatic setting
time
BQ CH1
CH192
629C
635B
25244
25435
7 R/W
3
C
10 to 250 seconds
60
1
When the RUN/STOP transfer (Identifier: SR, Resister address: 0133H) of the COM-ML becomes STOP, set lock becomes “0: Unlock.”
(i.e. The engineering setting data is writable.)
2
When using a non-specified CT, set to “1: CTL-12-S56-10L-N (0.0 to 100.0 A).”
3
When the set lock (Identifier: LK, Resister address: 5E0CH to 5E1BH) is set to “0: Unlock” (the RUN/STOP transfer of the COM-ML becomes
STOP), writing data is possible.
4
When using a non-specified CT, set the number of winds of the CT.
Continued on the next page.