C h a p t e r 3 : I n s t a l l i n g t h e D r i v e
3-25
AC890PX AC Drive
DIGITAL I/O
Name Range
Description
01
DIN1
0-24V DC
Digital Input 1 (default = JOG)
02
DIN2
0-24V DC
Digital Input 2 - (default = RUN)
03
DIN3
0-24V DC
Digital Input 3 - (default = STOP)
04
DIN4
0-24V DC
Digital Input 4 - (default = REVERSE)
05
DIN5
0-24V DC
Digital Input 5 - (default = TORQUE MODE)
06
DIN6
0-24V DC
Digital Input 6 - (default = unassigned)
07
DIN7
0-24V DC
Digital Input 7 - (default = unassigned)
08
DIN8/DOUT1
0-24V DC
Digital Input/output 1 -
(default = digital output: RUNNING)
X15
09
DIN9/DOUT2
0-24V DC
Digital Input/output 2 -
(default = digital output: ZERO SPEED)
All digital inputs/outputs are configurable using the DSE 890 (Drive System Explorer) Configuration Tool supplied on disk.
The table shows the factory defaults. The digital inputs require 24V DC which is supplied at terminal X14/03. For further
information refer to the DSE 890 Configuration Tool.
NOTE
The maximum permissible sum of currents from X14/03, X15/08, X15/09 is 150mA. The load on X15/08 & X15/09
connects from these pins to X14/04 (0V). An Alert message will be displayed if exceeded.
SUPPLY
150mA
X14/03
X15/08
X15/09
X15/01
X15/07
(7mA each)
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...