C h a p t e r 3 : I n s t a l l i n g t h e D r i v e
3-13
AC890PX AC Drive
2.1.1 Protective Earth (PE)/Ground Terminals (E)
Permanent Earthing
The unit must be
permanently earthed
according to EN 61800-5. For permanent earthing, EN 61800-5 states that:
A cross-section conductor of at least 10mm² copper or 16mm
2
aluminium is required.
Conductors must be sized in accordance with Local Wiring Regulations which always take precedence.
As a guide, refer to the Input Current for the drive given in the Electrical Ratings tables.
•
Fix the Drive earth connection(s) to
.
•
Fix the earth from the Motor to
.
2.1.2 3-Phase Connections (K)
•
Remove the supply fuses from the drive and connect the 3-phase supply in any order.
•
Branch fusing - not required.
Drive
Model
4/0215 4/0260 4/0300 4/0420 4/0480 4/0520 4/0580
460V
Tightening Torques
31Nm
31Nm 31Nm 31Nm 43Nm 43Nm 43Nm
Drive Model
6/1030
7/0130
6/0160
7/0160
6/0190
7/0190
6/0280
7/0280
6/0340
7/0340
575V
Tightening
Torques
26Nm 26Nm 31Nm 31Nm 31Nm
2.1.4 Motor/Output Connections (D)
•
Connect to the motor in any order.
Drive Model
all models
460V
575V
Tightening Torques
42.5Nm
Summary of Contents for AC890PX Series
Page 8: ......
Page 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Page 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Page 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Page 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Page 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Page 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Page 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Page 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...